Mr. Bernard P. Orlan April 11, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time environmental Measurements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 8:06 A.M. and concluded after 2:51 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 67.2 °F to 77.5 °F. Four (4) of the indoor measurements for temperature were below, twenty one (21) measurements were above, and sixty-three (63) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 53.2 to 64.9 °F.

Relative Humidity

The relative humidity indoors ranged from 28.1 percent to 42.8 percent. Sixteen (16) of the indoor measurements for relative humidity were below and seventy two (72) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 53.2 to 64.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 366 ppm to 1460 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COo concentration was 574 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1274 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. The highest levels of CO2 were detected in Gymnasium and Stair case A 7th floor were 1460 ppm, 1353 ppm respectively. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were between 0 to 4 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 1 ppm to 4 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 35 pg/m^ with an average 11 pg/m^ ■ None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 5 pg/m^ to 56 pg/m^ with an average of 25 pg/m^. None of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in

CONFIDENTIAL, CITY_2IMCl00_003462215 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259178

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259178Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →