Mr. Bernard P. Orlan June 14,2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Project No. 15-19125-0279
* file measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• ITie building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Twelve (12) of the indoor measurements for temperature were below the range of 73 to 79°F
(at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the
summer season.
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. None of the indoor respirable particulate measurements were above the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children.
5. Two of the indoor COt measurements were above the ASHRAE Standard 62-1999
recomimended maximum concentration of <700 ppm above the background level.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or212.