Mr. Bernard P. Orlan June 14,2002
Indoor Air Quality Assessment Page 3
P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measuremeyts
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50)
from inside the school building and ten (10) outdoors. All three floors of the school were
surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 7:00 AM and concluded after
12:47 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 72.3 °F to 75.6 °F. Twelve (12) of the
indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative
humidity) as recommended by ASHRAE Standard 55-1992 during the summer season, 'fhe
outdoor temperature measurements ranged from 62.1 °F to 62.4 °F.
Relative Humidity
The relative humidity indoors ranged from 47.7 percent to 51.7 percent. All of the indoor
measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity ranged from 46.1 percent to 46.2
percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 556 ppm to 1481 ppm. Two (2) of the
indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 700 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1400 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 2 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were
also 2 ppm for all readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 39 pg/m^ with an
average approximately 15 pg/m^- None of the measurements collected indoors for respirable
particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor
respirable particulate concentration ranged from 32 pg/m^ to 40 pg/m3 with an average of
approximately 38 pg/m^.