Mr. Bernard P. Orlan June 13, 2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Project No. 15-19125-0279
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO, CO2 and TVOCs were below applicable standards and guidelines.
2. Four (4) of the indoor measurements for temperature were below and two (2) were above the
range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard
55-1992 during the summer season.
3. Seven (7) of the indoor measurements for relative humidity were above the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. Four (4) of the indoor respirable particulate measurements were above the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or212.