Mr. Bernard P. Orlan June 13,2002
Indoor Air Quality Assessment Page 3
P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50)
from inside the school building and ten (10) outdoors. All three floors of the school were
surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 11:06 AM and concluded after
1:00 P.M.
Temperuii^
Indoor diy bulb temperature measurements ranged from 71.7 °F to 81.4 °F. Four (4) of the
indoor measurements for temperature were below and two (2) were above the range of 73 to
79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during
the summer season. The outdoor temperature measurements ranged from 84.8 °F to 84.9 °F.
Relative Humidity
The relative humidity indoors ranged from 48.4 percent to 61.3 percent. Seven (7) of the indoor
measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity ranged from 52.1 percent to 52.6
percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 526 ppm to 1261 ppm. All of the indoor
measurements were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 603 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1303 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were
also 1 ppm for all readings.
Res^irable^Particula^ tPM2 5)
Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 52 pg/m^ with an
average approximately 28 pg/m^- None of the measurements collected indoors for respirable
particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. Eight (8) of the indoor
measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive
individuals and children. The outdoor respirable particulate concentration ranged from 98 pg/m^
to 110 pg/m3 with an average of approximately 104 pg/m^.