NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, PS234M, May 29, 2002

Machine-extracted title · confidence 34%

ATC report of indoor air quality measurements at PS 234M; BOE program, May 29, 2002.

NYC-WTC_000315270–000315273
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 29, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 7:00 AM and concluded after 12:41 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 64.1 °F to 77.1 °F. Eleven (11) indoor measurements for temperature were below and forty (40) of the measurements were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature measurements ranged from 64 to 64. TF.

Relative Humidity

The relative humidity indoors ranged from 49.6 percent to 65.1 percent. One (1) of the indoor measurements for relative humidity was above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 65.1 to 65.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 512 ppm to 1028 ppm. All of the measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 523 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1223 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for all readings.

Respirable Particulates (PM2 5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 16 pg/m^ with an average approximately 11 pg/m^' None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 5 pg/m^ to 14 pg/m^ with an average of approximately 10 pg/m^.

CITY_21MC100_003032575

NYC-WTC_000315272

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000315272Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →