Mr. Bernard P. Orlan May 28, 2002
Indoor Air Quality Assessment Page 3
P. S. 234M ATC Project No. 15 -19125-0279
Real-Time Environmentai. Measi rements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one
(51) from nside the school building and nine (9) outdoors. All three floors of the school w ere
surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after
4:30 P.M.
TcDiperalim
Indoor dry bulb temperature measurements ranged from 68.0 °F to 74.6 °F. Thirty (30) indoor
measurements for temperature were below and twenty-one (21) of the measurements were within
the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard
55-1992 during the summer season. The outdoor temperature measurements ranged from 61 to
69 °F.
Rflcitive Hiti/iidity
The relative humidity indoors ranged from 35.6 percent to 44 percent. All of the indoor
measurements for relative humidity were within the ASIlRAE-recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity ranged from 44 to 47.6 percent.
Cdrhon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 545 ppm to 955 ppm. All of the
measurements were below' the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CE)2 concentration was 555 ppm. Therefore, the maximum acceptable level of CO2 at thi.s
location was 1255 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. fhe primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration.s were 1
ppm for all readings.
Respirable Particulates (RM2, jl
Respirable particulate concentrations* indoors ranged between 18 pg/m^ to 50 pg/m^ with an
average approximately 30 pg/m^- None of the measurements collected indoors for respirable
particulate concentrations were above the NPAAQS 65 pg/m-^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. Four (4) of the fifty-one (51)
instantaneous readings were above the USEPA recommended concentration of 40 pg/m^ for
sensitive individuals and children. The outdoor respirable particulate concentration ranged from
79 pg/m^ :o 90 pg/m^ with an average of approximately 82 pg/m^.