Mi'. Bernard P. Orlan May 28, 2902
tnilw'r .Air Quality Assessment Page 2
P S, 234M A I C Proicct No. 1 5-191 25-0279
ITe re,sult.s of the sampl ng represent eondition.s found on the dates of the survey and may not
represent conditions found at other times, fhe information presented in this repo t should be
used by the HOE as a g.iide to assess the need for further improvements m current indoor air
quality control activities.
t VALI A flONf’RITERIA
Currently, ’.here arc no regulatory standards for indoor air quality in non-industrial buildings,
■sLich as ofRces and schools. Tor the real-time data collected, Ad'C uses the commonly accepted
guidelines .nted m the following publications:
for Ac(ep,'t/h/e Ji/Aoor Air Oitofi/v (ASJfRAff 62A999), American Society of
Heating. Refrigerating, and Air-Conditioning Engineers (ASlIRy\E);
rii i‘i niaf Environ/iientdl t 'onAi lions for Hiimon Occupiincy (A Si {RAE 05-1992/;
« {fuitislricii //ygicnists (itiide to fndoor Air Qniilitv /nvcsii^ations (1993), Anscrican
Industrial Hygiene Association (AIHA).
'fable 1 lists target guidelines for the parameters that Ad'C evaluated during this investigation.
Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality
w 11 be achieved at all times.
TABLE 1
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL AGENCY OR
ORGANIZATION
t.'arbon fdo.xide <700 parts per million (ppm) ASH RAT 62
(COn)___________ above background level
Carbon Monoxide 9 ppm ASHRAF. 62 (adopted from
(CO) USTPA NPAAQS)
Respirable 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM?.5) ®24-hour average
40 pg/m^ 24-hour average USEPA - recommendation for
children/sensitive individuals
rcmperatiire Summer; 73-79°T at 50% RH ASI I RAT 55
Winter: 68-75°F at 50%, RH
Relative Humidity 30 - ASI IRAK 55
Total ViTatile
Organic Compounds 1 ppni AlllA
(TVOC)
L SEPA " Jnited States Environmental Protection Agency
\P,\AQS Rational Priniaiy Ambient-.Air Quality Standard
ARIA = American Industrial Hygiene Association