NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC reports IAQ measurements taken March 22, 2002 at High School for Leadership & [name].
NYC-WTC_000370553–000370556OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 25, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time E.wironmental Measurements
ATC collected one hundred and twenty-three (123) sets of real-time environmental measurements consisting of one hundred and seventeen (117) in the school building and six (6) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:30 A.M. and concluded after 2:42 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 59.7 °F to 75.8 °F. Seventeen (17) indoor measurement for temperature were above and two (2) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55- 1992 during the heating season (wintertime conditions). The outdoor temperature range was 33.2 °F to 35.0 °F.
Relative Humidity
The relative humidity indoors ranged from 16.2 percent to 36.6 percent. One hundred and fifteen (115) of the indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 22.5 to 24.4 percent.
Carbor. Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 358 ppm to 974 ppm. All of the indoor . measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 327 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1027 ppm (background level + 700 ppm).- Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
CarbonMonoxideConcenP'a^n
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm- 3 ppm.
Respirable Particulates (PM2_s)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 15 pg/m^ with an average 3 pg/m^- None of the indoor or outdoor measurements for PM2 5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 15 pg/m^ to 28 pg/m- with an average of 20 pg/m3.
CITY_21MC100_002865889
NYC-WTC_000370555
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260052
ATC report of IAQ measurements at the referenced school, March 22, 2002, for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399478
BOE-ordered IAQ measurements at 90 Trinity Place for High School for Leadership, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399528
June 10, 2002 IAQ measurements update letter to BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399496
Indoor air quality report for the referenced NYC BOE school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399254
Indoor air quality report dated May 7, 2002 for High School project; ATC.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291976
ATC IAQ measurements conducted June 4, 2002 for BOE at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399402
Indoor air quality measurements collected May 17, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291988
ATC IAQ measurements collected June 11, 2002 for the referenced BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211859
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 25, 2002, to evaluate possible contamination.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399504
Correspondence about IAQ measurements at the school, May 30, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000211859
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 25, 2002, to evaluate possible contamination.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296758
ATC IAQ measurements report for HS for Leadership & [name], Apr 12, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260052
ATC report of IAQ measurements at the referenced school, March 22, 2002, for BOE.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260329
ATC IAQ measurements at the referenced school, BOE request noted.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377102
Memobrief/letter reporting IAQ measurements at a NYC high school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260521
ATC IAQ measurements collected June 3, 2002 at the referenced school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
Similar indexed content
NYC-WTC_000260052
ATC report of IAQ measurements at the referenced school, March 22, 2002, for BOE.
Similar indexed content
NYC-WTC_000399478
BOE-ordered IAQ measurements at 90 Trinity Place for High School for Leadership, May 2002.
Similar indexed content
NYC-WTC_000399528
June 10, 2002 IAQ measurements update letter to BOE.
Similar indexed content
NYC-WTC_000399496
Indoor air quality report for the referenced NYC BOE school, May 2002.
Similar indexed content