Mr. Bernard P. Orlan March 25, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time E.wironmental Measurements

ATC collected one hundred and twenty-three (123) sets of real-time environmental measurements consisting of one hundred and seventeen (117) in the school building and six (6) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:30 A.M. and concluded after 2:42 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 59.7 °F to 75.8 °F. Seventeen (17) indoor measurement for temperature were above and two (2) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55- 1992 during the heating season (wintertime conditions). The outdoor temperature range was 33.2 °F to 35.0 °F.

Relative Humidity

The relative humidity indoors ranged from 16.2 percent to 36.6 percent. One hundred and fifteen (115) of the indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 22.5 to 24.4 percent.

Carbor. Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 358 ppm to 974 ppm. All of the indoor . measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 327 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1027 ppm (background level + 700 ppm).- Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CarbonMonoxideConcenP'a^n

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm- 3 ppm.

Respirable Particulates (PM2_s)

Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 15 pg/m^ with an average 3 pg/m^- None of the indoor or outdoor measurements for PM2 5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 15 pg/m^ to 28 pg/m- with an average of 20 pg/m3.

CITY_21MC100_002865889

NYC-WTC_000370555

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000370555Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →