Mr. Bernard P. Orlan June 04, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership' & Public Service (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 77.1 to 83.1 °F. Eighteen (18) of the indoor measurements for temperature were above and One hundred-ten (110) measurements were within the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 daring the summer season. The outdoor temperature ranged from 68.1 to 79.4 °F.
Relative Humidity
The relative humidity indoors ranged from 32.1 percent to 40.8 percent. All of the indoor measurement.s for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 26.9 to 30.1 percent.
CarhonHioxide Concentration
Carbon dioxide concentrations indoors ranged from 519 ppm to 1011 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 689 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1389 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide C oncentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm. These concentrations were below the NP/.AQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.
Respirable Particulates (PM2 5)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 7 pg/m^ with an average 3 pg/m-- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and childfen. The outdoor respirable particulate concentrations ranged from 20 pg/m^ to 42 pg/m^ with an average of 30 pg/rn^.
CONFIDENTIAL, CITY_21MC1OO_OO3464516 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260523
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000260517
ATC IAQ measurements collected May 31, 2002 at High School for Leadership & [name].
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260112
ATC IAQ measurements collected April 18, 2002, at the referenced school per BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410935
ISO/IEC quality systems-related material associated with project records.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410939
Documentation of accreditation scope for bulk asbestos analysis at ATC lab.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291976
ATC IAQ measurements conducted June 4, 2002 for BOE at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410919
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399402
Indoor air quality measurements collected May 17, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410915
IAQ measurements at 90 Trinity Place; BOE requested assessment of air quality.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399516
June 5, 2002 IAQ measurement report for Leadership & [name] at 90 Trinity Place.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291988
ATC IAQ measurements collected June 11, 2002 for the referenced BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188385
Memo reporting indoor air quality measurements collected at a school on June 7, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399496
Indoor air quality report for the referenced NYC BOE school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000410919
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410935
ISO/IEC quality systems-related material associated with project records.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260401
ATC IAQ measurements collected May 17, 2002 for BOE request.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260509
ATC report of indoor air quality measurements collected at the referenced school in May 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399512
June 4, 2002 IAQ measurements update letter to BOE for the school at 90 Trinity Place.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291972
ATC IAQ measurements at the referenced school, June 3, 2002, per BOE request.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000260517
ATC IAQ measurements collected May 31, 2002 at High School for Leadership & [name].
Similar indexed content
NYC-WTC_000260112
ATC IAQ measurements collected April 18, 2002, at the referenced school per BOE program.
Similar indexed content
NYC-WTC_000410935
ISO/IEC quality systems-related material associated with project records.
Similar indexed content
NYC-WTC_000410939
Documentation of accreditation scope for bulk asbestos analysis at ATC lab.
Similar indexed content
ATC IAQ measurements conducted June 4, 2002 for BOE at the referenced school.
Similar indexed content