IAQ report, High School for Leadership, Mar 2002

Machine-extracted title · confidence 55%

Indoor air quality measurements collected March 14, 2002 at the referenced school.

NYC-WTC_000370501–000370504
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 15, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOCConcentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO2, CO, and TVOCs were below applicable standards and guidelines. 2. Sixteen (16) indoor measurement for temperature were within the range and one hundred seventy-two (172) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Three (3) of the indoor measurements for relative humidity were below and one hundred eighty-five (185) were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4, All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^. All of the outdoor measurements were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 336 or 212.

^ncerely, Reviewed by: /ATC ASSOCIATES INC.

.Amel^aVal James R. Cohn, CIH, CSP Senior Iroject Manager Regional Manager Industrial Hygiene Division Attachment:

CITY_21MC100_002865791

NYC-WTC_000370504

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000370504Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259995

IAQ measurements collected Mar 14, 2002 for BOE

Similar indexed content

NYC-WTC_000399204

IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.

Similar indexed content

NYC-WTC_000370492

Indoor air quality measurements collected March 12, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →