Project Memorandum
ASSOCIATES INC.
Subject: 225 Rector Place
Re: Ambient Air Sampling
To: Peter Hoyle
Related Management
From: Fred Burkhardt
Date: December 3, 2001
On November 28, 2001, ATC collected one ambient air sample in each of the apartments listed below,
and one sample in five common hallways of the building, to ascertain the presence or absence of
airborne asbestos. All samples were collected and analyzed in accordance with the AHERA
Transmission Electron Microscopy (TEM) method as set forth at 40 CFR Part 763, Subpart E, Appendix
A.
Apartments sampled are identified in the following table.
Floor Apartments Floor Apartments
Penthouse G 11 D
23 H 10 C, D, Hallway
22 9
21 B.E 8
20 B, Hallway 7 G
19 J 6
18 5 S, Hallway
17 4 A. R.t
16 B 3 T
15 Hallway 2
14 T 1 D, Lobby
12 c Basement
In the absence of a specific ambient air standard, ATC has selected as a criteria for acceptable ambient
air sample sets, the AHERA re-occupancy requirement following an asbestos abatement action (rf an
average of less than 70 asbestos structures per square millimeter (<70 s/mm^) per sample set. This
criteria has been selected because the AHERA requirement is the most stringent reoccupancy
requirement available, and has been designed to be protective of children following an asbestos project
Based upon analytical sample results for all samples recording levels below the AHERA clearance
requirement, it is ATC's opinion that the ambient air samples collected throughout the building are
representative of the ambient conditions at the time of testing and that the areas tested meet an
acceptable criterion for re-occupancy. If you have any questions or require additional explaination of the
information presented please do not hesitate to call me at 212-353-8280.
Thank You.