Air quality testing at 88 Pine Street, Sep 2001

Machine-extracted title · confidence 42%

Environmental testing of building air quality and dust at 88 Pine Street after the World Trade Center event, Sept 2001.

NYC-WTC_000366617–000366618
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

All surfaces such as but not limited to the air-handling units, passenger and freight elevator lobbies, loading dock, main lobby, concourse level, roof top and cooling tower were wet wiped and HEPA vacuumed by a licensed asbestos contractor. All air filters within the said fan units were removed and disposed of as asbestos waste.

Please refer to the laboratory certificate of analysis for all samples collected.

In addition to the above, CTSI performed Indoor Air Quality testing fi-om various areas of the building. The testing was performed for Particulate, Carbon Monoxide & Dioxide, Temperature & Relative Humidity. Temperature & Carbon Dioxide (CO2) levels were slightly elevated due to building shut down. Relative Humidity, Carbon Monoxide and Dust Particulate levels are within the OSHA standards.

CO2 is a colorless, odorless, tasteless gas that results from a combustion or metabolic process. Low CO2 concentration levels (which come from people) are always present in buildings. At concentrations above 5,000 PPM in air, a loss of mental acuity will occur. CO2 levels greater than 1,000 PPM indicate the lack of fresh air and poor ventilation or over occupation. Highly susceptible populations (i.e., elderly, asthmatic, immunodeficient) will experience some discomfort at levels of 800 PPM and greater. Typical office levels for CO2 are listed between 300 and 800 PPM. All levels collected on September 25“’ ranged from 422 PPM to 706 PPM. Please refer to section VD.

The licensed asbestos contractor utilized for the project was Degmor, Inc. They have sent their documentation directly to your office.

Due to the outside air conditions with elevated dust levels and fumes from the clean up process, CTSI recommends that the outside fresh air louvers be kept closed and only opened when outside air has been checked by building engineering staff. Lack of fresh outside air will result in elevated Carbon Dioxide levels during building full occupancy after 10:00 AM. Tenants may report an increase in symptoms such as but not limited to headaches, mild dizziness and fatigue.

CTSI also, recommend the air filters on all fan units be inspected on a daily basis and if necessary, replaced during the outside clean up process. The cleaning contractor should only utilize HEPA filtered vacuums for building cleaning.

Furthermore, CTSI recommend periodic air quality monitoring during the outside clean up process.

Thank you for giving CTSI the opportunity to assist you on this project.

TIS I CITY_21MC100_002849959

NYC-WTC_000366618

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000366618Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →