NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 1 page

Ambient air sampling memo, Tribeca Towers, Jan 2002

Machine-extracted title · confidence 45%

ATC sampling memo detailing 14 ambient air samples at Tribeca Towers, Jan 2002.

NYC-WTC_000365799
Page image
Scanned page image, NYC-WTC_000365799
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Ambient Air Sampling ASSOCIATES INC.

Subject: Tribeca Towers 105 Duane Street Re: Ambient Air Sampling Location: Common Hallways during Duct Cleaning, 2"'^ floor Mechanical Room From: Fred Burkhardt Date: January 4, 2002

On December 27, 28 & 29, 2001, ATC collected a total of fourteen ambient air samples, ten from within common hallways and four within the 2"^^ floor mechanical room to ascertain the presence or absence of airborne asbestos. The sample methodology, quantity, and location were agreed upon between Related Management, ATC and H.A. Bader Consultants Inc. the tenants associations consultant. Samples were analyzed in accordance with the more stringent AHERA Transmission Electron Microscopy (TEM) method as set forth at 40 CFR Part 763, Subpart E, Appendix A. In the absence of a specific ambient air standard for asbestos, regulatory agencies have been using the AHERA re-occupancy requirement following an asbestos abatement action. This standard of an average of less than 70 asbestos structures per square millimeter (<70 s/mm^) per sample set is the most stringent reoccupancy requirement available, and has been designed to be protective of children following an asbestos project.

Based upon the analytical results from the 2"^ 5‘\ 10^ 15*, 20*. 25*. 27*. 34*. 41** floor hallways and 2"*^ floor mechanical room of no asbestos structures detected, which is below the AHERA clearance requirement. It is ATC’s opinion that duct­ cleaning activities did not result in elevated asbestos levels within those spaces, and the ambient conditions sampled are representative of the building at the time of testing and meet an acceptable criterion for occupancy. If you have any questions or require additional explaination of the information presented please do not hesitate to call me at 212-353-8280 extension 343.

Thank You.

CITY_21MC100_002849492

NYC-WTC_000365799

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000365799Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000365779

ATC sampling memo documenting asbestos sampling in hallways and mechanical room, Dec 2001.

Similar indexed content

NYC-WTC_000365774

Memo describing ambient air sampling at Tribeca Towers apartment 11D for asbestos, Jan 2002.

Similar indexed content

NYC-WTC_000363407

Ambient air sample collection details and AHERA-based criteria for acceptance.

Similar indexed content

NYC-WTC_000363410

ATC-DEP collaboration: ambient air samples collected within Tribeca Tower.

Similar indexed content

NYC-WTC_000365137

Memo on ambient air sampling at Tribeca Park, 400 Chambers Street, Nov 2001.

Similar indexed content

Compare copies and versions →