Tribeca Tower ambient air samples documentation, Dec 13, 2001

Machine-extracted title · confidence 44%

Ambient air sample collection details and AHERA-based criteria for acceptance.

NYC-WTC_000363407
Page image
Scanned page image, NYC-WTC_000363407
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document 12/13/2001 13:28 FAX 212 333 8306 ATC @002

WTC ASSOCIATES IN':. Ambient Air Sampling

Subject: Tribeca Towers 105 Duane Street Re; Ambient Air Sampling To: Peter Hoyle Related Management From: Fred Burkhardt < /p’ Date: December 13, 2001

On December 12, 2001, at the request of and witnessed by the NYCDEP, ATC collected a total of ten ambient air sample from within Tribeca Tower, Five samples were collected from the common hallway of the tenth floor, v/ith one sample placed directly in front of the supply air entry point. A second set of five ambient air samples were collected from the second floor air handler room servicing the common areas including the tenth floor. In the absence of a specific ambient air standard. ATC has selected as a criteria for acceptable ambient air sample sets, the AHEPA re-occupancy requirement following an asbestos abatement action of an average of less than 70 asbestos structures per square millimeter (<70 s/mm^) per sample set. This criteria has been selected because the AHERA requirement is the most stringent airborne asbestos reocciipancy standard available, and has been designed to be protective of children following an asber.tos abatement project.

Based upon analytical sample results for all samples recording no asbestos structures detected which is significantly below the AHERA clearance requirement. It is ATC's opinion that the ambient air samples collected from these areas are representative of the ambient conditions at the time of testing and that the areas tested meet an acceptable criterion for re-occupancy. If you have any questions or require additional explaination of the information presented please do not hesitate to call me at 212-353-8280. w• Thank You,

CITY_21MC100_003754738

NYC-WTC_000363407

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000363407Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000363410

ATC-DEP collaboration: ambient air samples collected within Tribeca Tower.

Similar indexed content

NYC-WTC_000365774

Memo describing ambient air sampling at Tribeca Towers apartment 11D for asbestos, Jan 2002.

Similar indexed content

NYC-WTC_000365779

ATC sampling memo documenting asbestos sampling in hallways and mechanical room, Dec 2001.

Similar indexed content

NYC-WTC_000365799

ATC sampling memo detailing 14 ambient air samples at Tribeca Towers, Jan 2002.

Similar indexed content

NYC-WTC_000363386

Summary of sampling observations and ambient air monitoring at Tribeca Tower.

Similar indexed content

Compare copies and versions →