FDNY spill at Barclay Street, Sept 2001

Machine-extracted title · confidence 46%

Preliminary report of a potential asbestos and transformer oil release at a substation site.

NYC-WTC_000355951–000355957
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Environmental Detailed Incident Report

Detailed Description: ******#****«*«**«**«**i*4i«*#*************#***4i******«*****«*«**»*««*»*«*««**4>****ii**4:****«*****«»«*««*****«***)fE*******«*4*«**«*«**«*«*

Update 9-12-01 @ 07:35 . D Connelly #80483 reports that 2000 gallons of dielectric fluid has leaked based on the tank levels of dielectric feeders. C!G J Fox notified @ 07:46. •J Moran #0!!82

9-12-01,08:15

Updates were made concerning the 2,000 gallons to NRC, DEC, DEP, and FDNY Marine agency hotlines. Jane O'Connell was left a message. Second notifications were made concerning the asbestos and initial potential oil release from the substation.

Mike Kessler, #79686

9-12-01,08:56

At 08:47 Dennis Connelly called to ensure FDNY was notified of potential PCB in dielectric fluid. Called Fire Fighter Tanzman at FDBCO, and notified him of 30,000 gallons of dielectric fluid with possible PCBs in the oil, asbestos, and SF6 gas. Called Bill Wallace who will be going to the location, and he will re­ notify the FDNY personnel on-location.

Mike Kessler, #79686

9-12-01,08:48

J. Fox of CIG notified DEP RTK of RQ release of asbestos, and potential RQ of PCBs.

Mike Kessler, #79686

9/13/01 I2:l6 - update provided by Joe Susco, EHS Manager Substation Operations: There are 9 transformers in the station, containing about 100,000 gallons of transformer oil and containing other oil filled components, such as bushings.

The amount of asbestos containing materials in the station is not known, but can include wiring, arc proof tape, transite board and other materials.

This station also has one dielectric fluid pumphouse containing a 7500 gallon tank and oil filled piping. There are also five 138kv oil filled feeders entering the station. Feeder oil is composed of 75% or greater alkylbenzene derivatives. There are also six capacitor banks in the station containing a total of about 3600 o gallons of capacitor oil. H K I In addition to oil, this station contains lead-acid batteries and Sulfur Hexafluoride gas filled switches. The total amount of sulfuric acid (30% concentration) is

I o approximately 390 gallons and the amount of SF6 gas is about 220 pounds.

The station also stored or used a small amount of gasoline (up to 100 lbs), compressed nitrogen (up to 1,000 lbs) and pcb containing waste (up to 100 lbs). o These amounts were obtained from the 2001 SARA report. Io C. Koehler 84220 o co

E2MIS 24-SEP-2001 08:13:23 Page 2 of 7

NYC-WTC_000355952

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000355952Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000130438 · Box DEP Box 53

Draft special investigative audit report on environmental data from the World Trade Center site prepared by IT Corporation.

Similar indexed content

Compare copies and versions →