DOHMH memo detailing October 2001 air monitoring results for indoor contaminants.
12 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗DOHMH preliminary summary of IAQ measurements on 22nd floor at 225 Broadway.
NYC-WTC_000354112–000354114OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
990 fpm with an average air velocity of 705 fpm; along the east side ranged frorji 154 fpm to 448 fpm with an average air velocity of 294 fpm; and along the west side ranged from 188 fpm to 995 fpm with an average air velocity of 570 fpm. All of the air velocity measurements indicated that the ducted supply mechanical ventilation system that serves the space was functioning efficiently.
Noise levels along the north side of the space ranged from 47.0 dBA to 55.9 dBA; along the south side ranged from 45.1 dBA to 46.6 dBA; along the east side ranged from 50.3 dBA to 51.2 dBA; along the west side ranged from 48.3 dBA to 49.0 dBA; and within the interior ranged from 49.0 dBA to 50.0 dBA. All of the levels were well below the PEL of 85 dBA.
Other
Significant dust accumulation that was consistent in appearance with residual dust from adjacent ambient areas was observed on the window ledges along the south side of the space (facing Broadway). The accumulation was likely due to secondary setting/sedimentation. HEPA vacuuming and wet cleaning techniques should be used by the building management to prevent and/or minimize airborne dust from this area from permeating the rooms immediately adjacent to the affected area on the 22"^* floor. Vacuuming by conventional means is unacceptable since this practice would render the dust airborne. Wet cleaning with a high-phosphate content (containing at least 5% trisodium phosphate (TSP) have been found to be effective when used as part of final clean up. TSP detergents are commonly found in hardware stores. It is im.portant to note that lead dust adheres very tenaciously to rough or porous materials such as wood surfaces and masonry surfaces (particularly concrete).
Impressions
The results indicated that all of the air monitoring parameters that were detected was either well below or within permissible exposure limits. Of interest, no asbestos fibers were detected and no phosgene was detected. No detectable levels of irritants, asphyxiants, and volatile organic chemicals (VOC’s) were noticeable. A slight and continuous smell of smoke throughout the space may be a nuisance to occupants. The overall air monitoring results suggest that the air in the space was not compromised by the acute exposures with regards to air contaminants from the surrounding areas and furthermore, the space is safe for occupancy. The Environmental Affairs Unit will continue to monitor the air in the space in the event that there are health concerns from occupants regarding possible chronic exposures with regards to air contaminants.
cc: C. Kainbili MD J. Slade P. Kellner RN M. Dorsinville RN S. Mirsky
CITY_21MC100_006717314
NYC-WTC_000354114
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000354092
DOHMH memo detailing October 2001 air monitoring results for indoor contaminants.
12 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000279307
Preliminary indoor air monitoring results for 225 Broadway floor near WTC site.
12 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000321987
DOH/DMH air monitoring on 23rd floor of 225 Broadway; detailed results and table in report.
12 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000106330
Letter reporting asbestos testing results for air and dust at Borough of Manhattan Community College in February 2002.
9 shared non-person entities · 1 shared topics · similarity 0.955
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000408671
Indoor air/dust tests after WTC collapse; metals, PCBs, dioxin analyses; one sample above standard.
7 shared non-person entities · 1 shared topics · similarity 0.945
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000106406
Memo detailing periodic environmental testing for asbestos, lead, silica, and dust at BMCC conducted in December 2001.
6 shared non-person entities · 1 shared topics · similarity 0.944
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000360376
Law Department Appendix K: indoor air and dust test results after WTC collapse.
8 shared non-person entities · 1 shared topics · similarity 0.944
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000243565
EIA report for Law Department project at 100 Church Street by TRC.
9 shared non-person entities · 1 shared topics · similarity 0.943
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000243668
Environmental assessment prepared for NYC Law Department by TRC Engineers, April 8, 2002.
9 shared non-person entities · 1 shared topics · similarity 0.943
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000243703
Environmental assessment prepared for NYC Law Department by TRC Engineers, April 8, 2002.
9 shared non-person entities · 1 shared topics · similarity 0.943
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000232952
Chain of custody documentation for samples collected in September 2001 involving multiple New York locations and consulting firms.
5 shared non-person entities · 1 shared topics · similarity 0.943
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000366617
Environmental testing of building air quality and dust at 88 Pine Street after the World Trade Center event, Sept 2001.
4 shared non-person entities · 1 shared topics · similarity 0.943
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000354092
DOHMH memo detailing October 2001 air monitoring results for indoor contaminants.
Similarity score 0.958 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000321987
DOH/DMH air monitoring on 23rd floor of 225 Broadway; detailed results and table in report.
Similarity score 0.958 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000185979
Report from ATC Associates detailing indoor air quality measurements collected at PS 89M for the Board of Education.
Similarity score 0.953 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313447
ATC IAQ measurements at P.S. 89M; BOE evaluation, April 11, 2002.
Similarity score 0.950 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000411145
ATC report of IAQ measurements at PS 89M requested by BOE; June 5, 2002.
Similarity score 0.950 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296758
ATC IAQ measurements report for HS for Leadership & [name], Apr 12, 2002.
Similarity score 0.950 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
DOHMH memo detailing October 2001 air monitoring results for indoor contaminants.
Similar indexed content
Preliminary indoor air monitoring results for 225 Broadway floor near WTC site.
Similar indexed content
NYC-WTC_000321987
DOH/DMH air monitoring on 23rd floor of 225 Broadway; detailed results and table in report.
Similar indexed content
NYC-WTC_000106330
Letter reporting asbestos testing results for air and dust at Borough of Manhattan Community College in February 2002.
Similar indexed content
NYC-WTC_000408671
Indoor air/dust tests after WTC collapse; metals, PCBs, dioxin analyses; one sample above standard.
Similar indexed content