Indoor Air Quality Preliminary Summary, 225 Broadway, Oct 2001

Machine-extracted title · confidence 31%

DOHMH preliminary summary of IAQ measurements on 22nd floor at 225 Broadway.

NYC-WTC_000354112–000354114
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

since there was no damaged friable suspect asbestos containing material (.ACM) from which bulk samples could be obtained. Suspect ACM including ceiling tile and thermal system insulation (TSI) were either intact or enclosed and were in good condition. Wipe samples for possible surface contamination with respect to Pb were collected and analyzed using NIOSH analytical method #9100 which utilizes Atomic Absorption Spectrometry (AAS). These samples were obtained from windowsills.

Temp and RH were measured using a Thermohygrometer. Air velocity was measured using a Velocical Meter. Noise levels were measured using an Ametek Sound Level Meter (SLM).

Summary of Results

No levels/concentrations of COCl 2, CI2, NH3, SO2, NO2, H2S, HCHO, O3, Hg, and natural gas were detected throughout the space on the 22"*^ Floor. Trace concentrations of (< 0.1 ppm) of HC including paraffins were detected in the space. The levels were negligible.

CO levels within the range of 1.0 ppm to 10 ppm were detected within the space. These levels were well below the PEL 8hr-time weighted average (TWA) of 35 ppm, ceiling exposure limit (C) of 200 ppm, and immediately dangerous to life and health limit (IDLH) of 1200 ppm. Background (ambient) level of CO is approximately 0.19 ppm.

CO2 levels within the range of 450 ppm to 500 ppm were detected. These levels were well below the PEL of 5000 ppm. Background (ambient) level of CO2 is approximately 350 ppm. The CT level was 21% (normal). The level suggests that the air was neither deficient nor enriched.

Phase Contrast Microscopy results indicated that no asbestos fibers were detected (ND) throughout the space. The minimum limit of detection (LOD) for the laboratory was 0.003 fiber/cc. The PEL is 0.1 fibers/cc. The most recent ambient airborne asbestos result from samples that were taken by EPA in Lower Manhattan was 29.6 fibei7m7

Atomic Absorption Spectrometry results indicated that Pb levels within the range of 2.5 ug/wipe'to 18.7ug/wipeAvcrc detected on windowsills. However, these levels were well below the HUD guideline of 500 ug ff’.

Temp and RH along the north side of the space ranged from 64.2 °F to 74.9 °F and 40% and 55% respectively; along the south side ranged from 71.0 °F to 72.0 °F and 30% to 31% respectively; along the east side ranged from 70.5°F to 70.8°F and 30% to 31% respectively; along the west side ranged from 72.4°F to 74,6°F and 30% to 31 % respectively; and within the interior ranged from 72.1 °F to 73.0 °F and 30% to 31 % respectively. Temp and RH were maintained within recommended guidelines.

Air velocity measurements along the north side of the space ranged from 168 fpm to 800 fpm with an average air velocity of 328 fpm; along the south side ranged from 360 fpm to

CITY_2IMCl00_006717313

NYC-WTC_000354113

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000354113Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000354092

DOHMH memo detailing October 2001 air monitoring results for indoor contaminants.

Similar indexed content

NYC-WTC_000279307

Preliminary indoor air monitoring results for 225 Broadway floor near WTC site.

Similar indexed content

Compare copies and versions →