NYC 9/11 Public Portal Document

Furthermore, the CO2 levels suggest that ventilation was not compromised. CO2 is often used as a surrogate to determine ventilation adequacy. Where ventilation is compromised, CO2 usually exceeds 1,000 ppm.

Noise Levels

Noise levels that were measured throughout the space ranged from 45.9 dBA to 51.5 dBA. The average noise level was 50.0 dBA. In all cases, the levels were well below the PEL of 85 dBA. The noise levels suggest that there was no likelihood of occupants been adversely effected by ambient noise that may arise from construction activities in or around the sunounding area. Based on this finding, personal air monitoring, audiometric testing, and personal protective equipment are unwarranted.

Odor Thresholds

No characteristic odors with respect to COCI2, H2S, NH3, Ch, SO2, mercaptan-like substances, and HCHO were noticeable. In fact, no levels of these contaminants were detected to support odor intensity. Additionally, there was no characteristic odor to suggest the presence or occurrence of biodecomposed matter.

Other

Dust accumulation that was consistent in appearance with dust from adjacent ambient areas was observed on the window ledges. The accumulation was likely due to secondary sedimentation. It is important to note that the windows were closed at the time of this air monitoring.

Precautionary Remediation Measures

At the time of the air monitoring, the ceiling diffusers were retrofitted with clean filters in preparation for the operation of the mechanical ventilation system. The floor was HEPA vacuumed prior to air monitoring. As part of a building wide cleaning effort, the building management began to clean the windows and the window ledges throughout the building. The cleaning is still ongoing. Impressions

Based on these results, no levels of most of the parameters were detected. Where levels of a few contaminants were detected they were either well below permissible exposure limits or within acceptable range. The air velocity measurements indicated that the mechanical ventilation system was not in full operation. The carbon dioxide levels suggest that despite the low velocity measurements, ventilation was not compromised. This finding is not unusual since the space was unoccupied and human bioeffluent therefore was not a factor.

CITY_21MC100_011096284

NYC-WTC_000321990

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000321990Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000354092

DOHMH memo detailing October 2001 air monitoring results for indoor contaminants.

Similar indexed content

NYC-WTC_000279307

Preliminary indoor air monitoring results for 225 Broadway floor near WTC site.

Similar indexed content

NYC-WTC_000354112

DOHMH preliminary summary of IAQ measurements on 22nd floor at 225 Broadway.

Similar indexed content

Compare copies and versions →