NYC 9/11 Public Portal Document
Three samples of debris from beneath the rubber mats in the playground were all found to
contain between a trace and 0.25 percent asbestos. Based on these results, the SCA
contracted for the removal and cleaning of the rubber mats and the playground surfaces.
There were a total of 13 soil samples collected from planters for analysis of asbestos.
Nine surface soil samples were found to contain either no detectable asbes*"s or trace
levels of asbestos. Four samples collected from a depth of six inches below the ground
surface were all found to contain no detectable asbestos. Based on these results, the SCA
Contracted for the removal and replacement of the surficial soils in all the planters around
the school.
School-Wide Lead Dust Sampling (November 29,2001)
To evaluate the adequacy of cleaning, an extensive dust sampling program was
implemented for analysis of lead. On November 29, forty dust samples were collected
from throughout the school for lead analysis. Of thefoity 'samples; 37 cohtained no
'detectablelead,? The-remaining three samples contained bet.ween 4.8 and. 17.>9 ug/ft^, J
which t^ejail .less thanjheffridst^frihgent .acceptable level.established for lead abatement
• projects, 40 ug/ft-?^'^
Follow-Up Air Monitoring for Asbestos (November 29-December 2,2001)
Eighteen air;samples were collected on each day during the period November 29 to
December 2. Samples were taken from various locations throughout the school. No’ ’
asbestos’sfructures. were .detected in any of the samples collected on those four days.
Initial Indoor Air Quality Assessment (November 29-December 2, 2001)
Independent of the sampling requested by ENVIRON on behalf of the PS 234 Parent
Teacher Association, the Board of Education retained ATC Associates Inc. to perform air
testing during the period November 29 through December 2, 2001. This testing included
the collection of four air samples (three inside the school and one outside the school) per
day for analysis of eleven metals and a niunber of hydrocarbon compoimds, including
benzene and other volatile organic compounds, as well as monitoring for other air quality
parameters, such as carbon dioxide, carbon monoxide, total volatile organic compounds,
and particulates (PM2.5). Sampling locations varied on each of the four days and
included the following locations:
• November 29: cafeteria, library, Room 305, outside on the east side of PS
234.
• November 30: Room 111, Room 229, Room 329, outside on the north side of
PS 234.
• December 1: Room 122, Room 222, Room 322, outside on the roof by the
HVAC intake.
2
CITY_21MC1OO_OO6'7 53558
NYC-WTC_000337662
OCR can misread numbers and units. Confirm readings against the page image before using them.