NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 3 pages

Lead dust wipe sampling, Stuyvesant HS, Feb 2002

Machine-extracted title · confidence 28%

NYC BOE environmental health sampling; dust wipe lead testing.

NYC-WTC_000336767–000336769
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Scope of Work

ATC Associates, Inc. (ATC) was retained by New York City Board of Education (NYC- BOE) to collect dust wipes to be analyzed for lead content. Dust wipe samples were collected from inside the distribution air ducts and mixing boxes in air handling units as per the request of NYC-BOE.

The purposed of the dust wipe sampling is to determine if dust in the distribution air ducts and mixing boxes in the air handling units contains lead.

ATC’s representative Mr. Yiannis Efstathiou visited Stuyvesant H.S. (M477) located at 345 Chambers Street, New York, NY on February 13*'’, 2002. Dust wipe.s to be analyzed for lead content were collected from inside the distribution air ducts and mixing boxes in air handling units indicated to ATC by the New York City Board of Education Environmental Health & Safety Unit and in accordance with HUD protocols.

LEAD-IN-D UST SAMPLING

Lead-in-dust threshold levels The New York City Health Code, part 173.14 and the Federal Departments of Housing and Urban Development (HUD) and Environmental Protection Agency (EPA) have established acceptable lead-in-dust levels for re-occupancy after a lead abatement has occun-ed (commonly refened to as “final clearance” levels). As stated in the Code, final clearance after abatement has taken place is achieved when dust wipe samples indicate lead levels below those listed below:

For Window wells: 400 pg/ft- For Windov/sills: 250 ug/fr For Floors: 40 pg/fV

Although the lead-in-dust samples collected at Stuyvesant H.S. (M477) were not collected in response to lead abatement and also were not collected from either floor, windowsill or a window well surface but rather from inside the distribution air ducts and mixing boxes in the air handling units, tire same tliresholds are used since no other regulations or standards are applicable to this project.

Sampling Methodology ATC provided all laboratory analytical services in support of this limited inspection. ATC is certified by the New York State Department of Health’s Environmental Laboratory Accreditation Program to perform lead and related analyses of environmental samples (Laboratory ID Number: 10879). The laboratory utilizes the United States Environmental Protection Agency analysis method number SW846-7420 and the National Institute of Occupational Safety and Health method number 7082M.

Stuyvesant H.S. (M477) February 23, 2002

CITY_21MC100_003072877

NYC-WTC_000336768

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000336768Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →