Indoor air quality report, Stuyvesant HS, Apr 2002

Machine-extracted title · confidence 40%

ATC IAQ measurements collected at Stuyvesant High School on Apr 29, 2002.

NYC-WTC_000336294–000336297
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 30, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (M477) ATC Project No. 15-19125-0246 In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 2 - 9 pg/m^ with an average of approximately 7 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration TVOCs inside the building wereO.O ppm for all readings. Dre outdoor TVOC concentrations were also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented: 1. Concentrations of respirable particulates, CO , and TVOCs were below applicable standards and guidelines. T 2. One-hundred and thirteen (113) of the indoor measurements for temperature were below and five (5) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. All indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Two (2) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading was taken in room 835 at 11:40 AM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education, If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely,

J TC ASSOCIA r£S INC. Reviewed by>

■Amel Ja^y James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CrTY_21MC100_003061261 NYC-WTC_000336297

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000336297Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →