Mr. Bernard P. Orlan May 20, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (M477) ATC Project No. 15-19125-0246
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2_5 concentration range for these rooms was 22 - 30 pg/m^ with an average of approximately 26 pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Concentration
TVOCs inside the building were 0.0 ppm for all readings. The-outdoor TVOC concentrations were also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of indoor respirable particulates, CO , and TVOCs were below applicable standards and guidelines. 2. All measurements of relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 3. One hundred (100) indoor temperature measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 4. Twenty-nine (29) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
CITY_21MC100_003060816
NYC-WTC_000336116
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406827
May 22, 2002 IAQ report for Stuyvesant High School, Board of Education project 15-19125-0246.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406788
Indoor air quality measurements at Stuyvesant High School conducted May 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336131
May 20, 2002 IAQ measurements at Stuyvesant High School for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406805
May 20, 2002 report of indoor air quality measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000213118
Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on June 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336141
May 22, 2002 IAQ measurements at Stuyvesant High School for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373107
Indoor air quality measurements collected at Stuyvesant High School in June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229474
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372955
ATC IAQ report for Stuyvesant High School (M477) dated May 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407007
ATC IAQ report to NYC Board of Education for Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335989
IAQ measurements collected June 20, 2002 at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373102
ATC indoor air quality measurements report for Stuyvesant High School dated June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000406788
Indoor air quality measurements at Stuyvesant High School conducted May 17, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406827
May 22, 2002 IAQ report for Stuyvesant High School, Board of Education project 15-19125-0246.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372955
ATC IAQ report for Stuyvesant High School (M477) dated May 23, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336131
May 20, 2002 IAQ measurements at Stuyvesant High School for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372950
ATC IAQ measurements collected on May 21, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406822
Report of IAQ measurements collected May 21, 2002 at Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406827
May 22, 2002 IAQ report for Stuyvesant High School, Board of Education project 15-19125-0246.
Similar indexed content
NYC-WTC_000406788
Indoor air quality measurements at Stuyvesant High School conducted May 17, 2002.
Similar indexed content
May 20, 2002 IAQ measurements at Stuyvesant High School for BOE.
Similar indexed content
NYC-WTC_000406805
May 20, 2002 report of indoor air quality measurements at Stuyvesant High School.
Similar indexed content
Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on June 14, 2002.
Similar indexed content