ATC IAQ measurements collected at Stuyvesant High School on Apr 29, 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements at Stuyvesant High School, April 2002, by ATC Associates for DOE.
NYC-WTC_000406646–000406649OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 30, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (M477) ATC Project No. 15-19125-0246 In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 2-9 pg/m^ with an average of approximately 7 pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Concentration TVOCs inside the building wereO.O ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented: 1. Concentrations of respirable particulates, CO , and TVOCs were below applicable standards and guidelines. ’ 2. One-hundred and thirteen (113) of the indoor measurements for temperature were below and five (5) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. All indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Two (2) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading was taken in room 835 at 11:40 AM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or212.
Sincerely,
A TCASSOCIA TES INC. Reviewed by^
Arnel Ja^Y James R. Cohn, CIH, CSP Senior Jh/ject Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_002902883
NYC-WTC_000406649
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000336294
ATC IAQ measurements collected at Stuyvesant High School on Apr 29, 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406666
Indoor air quality measurements at Stuyvesant High School, May 2002, for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336056
IAQ measurements collected May 1, 2002 for Stuyvesant High School; BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406675
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336289
ATC IAQ report for Stuyvesant High School; March 4, 2002 entry.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336060
IAQ measurements collected May 2, 2002 for Stuyvesant High School; BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336268
ATC reports IAQ measurements collected at Stuyvesant High School on Apr 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406695
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406560
April 15, 2002 memo referencing IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372924
ATC delivers IAQ report for Stuyvesant High School (M477) dated May 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372779
Indoor air quality measurements collected at Stuyvesant High School, April 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372830
Indoor air quality report for Stuyvesant High School dated May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000336294
ATC IAQ measurements collected at Stuyvesant High School on Apr 29, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406729
IAQ measurements at Stuyvesant High School, May 10, 2002, for DOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372847
Indoor air quality measurements collected May 6, 2002 at Stuyvesant High School.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406788
Indoor air quality measurements at Stuyvesant High School conducted May 17, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406679
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406600
April 22, 2002 memo documenting IAQ measurements at Stuyvesant High School.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000336294
ATC IAQ measurements collected at Stuyvesant High School on Apr 29, 2002.
Similar indexed content
NYC-WTC_000406666
Indoor air quality measurements at Stuyvesant High School, May 2002, for DOE.
Similar indexed content
NYC-WTC_000336056
IAQ measurements collected May 1, 2002 for Stuyvesant High School; BOE request.
Similar indexed content
NYC-WTC_000406675
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
Similar indexed content
NYC-WTC_000336289
ATC IAQ report for Stuyvesant High School; March 4, 2002 entry.
Similar indexed content