NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 30 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)_______________ ATC Project No. 15-19125-0246 Real-Time Environmental Measurements

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 1.15 P.M.

Temjieratw-e

Indoor dry bulb temperature measurements ranged from 68.4 °F to 73.7 °F. One-hundred and two (102) of the indoor measurements were below and sixteen (16) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature was 68.6 to 75.7 °F.

Relative Humidity

The relative humidity indoors ranged from 54.7 percent to 65.8 percent. One-hundred and eleven (111) of the indoor measurements for relative humidity were above and seven (7) of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 74.1 and 76.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 428 ppm to 1196 ppm. Twenty (20) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 372 ppm and 380 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1080 ppm (background level + 700 ppm). The highest reading was taken in room 1006 at 12:30 PM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 0 ppm for both readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 27 pg/m^ to 42 pg/m^ with an average of approximately 34 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the one hundred and eighteen (118) instantaneous indoor readings were above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 81 and 88 pg nC.

CITY_21MC100_003060948 NYC-WTC_000336161

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000336161Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000213095

Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 28, 2002.

Similar indexed content

NYC-WTC_000336153

May 28, 2002 IAQ measurements at Stuyvesant High School.

Similar indexed content

Compare copies and versions →