Mr. Bernard P. Orlan May 29 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)_____________ ATC Project No. 15-19125-0246 Real-Time Environmental Measurements

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 10:25 A.M. and concluded after 2:35 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.6 °F to 74.1 °F. Ninety-nine (99) of the indoor measurements were below and nineteen (19) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature range was 68,5 to 75,0 °F.

Relative Humidity

The relative humidity indoors ranged from 54,6 percent to 65,1 percent. Sixty-two (62) of the indoor measurements for relative humidity were above and none of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 55.8 and 65.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 465 ppm to 1196 ppm. Eight (8) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 386 ppm and 435 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1135 ppm (background level -t- 700 ppm). The highest reading was Uken in room 1004 at 2:35 PM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 1 ppm for both readings.

Respirable Particulates (PM2,j)

Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 24 pg/m^ with an average of approximately 19 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 18 and 41 pg/m^.

CITY_21MC100_002868702

NYC-WTC_000213097

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000213097Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →