Mr. Bernard P. Orlan May 31, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)_______________ ATC Project No. 15-19125-0246 Real-Time Environmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 1:00 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.7 °F to 73.7 °F. Ninety-eight (98) of the indoor measurements were below and none of the measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature was 70 to 75.2 °F.
Relative Humidity
The relative humidity indoors ranged from 54.6 percent to 65.8 percent. Ninety-seven (97) of the indoor measurements for relative humidity were above and none of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 68.4 and 70.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 420 ppm to 1189 ppm. Thirteen (13) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 336 ppm and 380 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1080 ppm (background level + 700 ppm). The highest reading was taken in room 1024 at 12:35 PM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 ppm to 1 ppm.
Respirable Particulates (PM2 H
Respirable particulate concentrations* indoors ranged between 28 pg/m^ to 40 pg/m^ with an average of approximately 33 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 67 and 74 pg/m3.
CITY_21MC1OO_OO29O3136
NYC-WTC_000406903
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000336148
May 2002 IAQ measurements at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335989
IAQ measurements collected June 20, 2002 at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229474
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406878
May 29, 2002 IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373102
ATC indoor air quality measurements report for Stuyvesant High School dated June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335929
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407013
ATC report of IAQ measurements conducted June 20, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406861
May 28, 2002 IAQ report for Stuyvesant High School under ATC project 15-19125-0246.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335940
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406970
Indoor air quality measurements at Stuyvesant High School prepared for Board of Education, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373107
Indoor air quality measurements collected at Stuyvesant High School in June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406953
ATC IAQ report for Stuyvesant High School to NYC Board of Education, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
May 2002 IAQ measurements at Stuyvesant High School for BOE.
Similar indexed content
NYC-WTC_000335989
IAQ measurements collected June 20, 2002 at Stuyvesant High School for BOE.
Similar indexed content
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 23, 2002.
Similar indexed content
NYC-WTC_000406878
May 29, 2002 IAQ measurements at Stuyvesant High School.
Similar indexed content
NYC-WTC_000373102
ATC indoor air quality measurements report for Stuyvesant High School dated June 2002.
Similar indexed content