Mr. Bernard P. Orlan May 31,2002 Indoor Air Quality Measurements Page 4 StUYvesant High School (MA??) ATC Project No. 15-19125-0246

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 27 - 35 pg/m^ with an average of approximately 33 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs inside the building were 0.0 ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The barge operation at Pier 25 has been shut down.

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Ninety-eight (98) of the indoor measurements were below and none of the measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 3. Ninety-seven (97) of the indoor measurements for relative humidity were above and none of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Thirteen (13) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading was taken in room 1024 at 12:35 PM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. 5. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommendation of 40 pg/m^ for sensitive individuals and children.

CITY_21MC100_002903137

NYC-WTC_000406904

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000406904Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000336148

May 2002 IAQ measurements at Stuyvesant High School for BOE.

Similar indexed content

NYC-WTC_000229474

Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 23, 2002.

Similar indexed content

Compare copies and versions →