Mr. Bernard P. Orlan November 20, 2001 Indoor Air Quality Assessment Page 3 Murray Bergtraum High School (M520) ATC Project No. 15-19125-0286
Real-Time Environmental Measurements
ATC collected one hundred and eighty-two (182) sets of real-time environmental measurements consisting of one hundred and eighty (180) in the school building and two (2) outdoors. All seven floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 7:00 A.M. and concluded after 3; 00 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.1 °F to 78.3 °F. Twenty-eight (28) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 51.8 and 61..0 °F.
Relative Humidity
The relative humidity indoors ranged from 44.5 percent to 55.4 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 50.8 to 82.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 494 ppm to 1077 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 408 and 420 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1120 ppm (background level 4- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0-1 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 59 pg/m^ with an average of approximately 29.5 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 57 and 125 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_003275077
NYC-WTC_000330336
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
13 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311765
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
11 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271154
UAQ indoor air quality assessment report for Stuyvesant High School in Oct 2001.
12 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323914
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312075
Indoors air quality assessment report for Stuyvesant High School dated November 16, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
11 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311783
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
12 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311814
ATC letter transmitting IAQ assessment results for Stuyvesant HS.
11 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311979
Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.983
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.982
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
12 shared non-person entities · 1 shared topics · similarity 0.982
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311292
ATC report of IAQ measurements at Stuyvesant High School (M477).
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271345
Letter from ATC to BOE about IAQ assessment at Stuyvesant High School, Nov 13, 2001.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410283
IAQ measurements report for PS 234M dated Jan 30-31, 2002.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396261
ATC report of IAQ measurements at PS 234M, January 2002.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
Similar indexed content
NYC-WTC_000311765
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
Similar indexed content
UAQ indoor air quality assessment report for Stuyvesant High School in Oct 2001.
Similar indexed content
NYC-WTC_000323914
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
Similar indexed content
NYC-WTC_000312075
Indoors air quality assessment report for Stuyvesant High School dated November 16, 2001.
Similar indexed content