Mr. Bernard P. Orlan January 29, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-four (54) from inside the school building and six (6) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 1:00 P.M. and concluded after 3:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 65.1 °F to 75.6 °F. Twenty-nine (29) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from, 58.1 to 60.3 °F.

Relative Humidity

The relative humidity indoors ranged from 22.3 percent to 32.6 percent. Forty (40) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 27.1 to 27.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 493 ppm to 584 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged 479 to 510 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1179 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school building was not occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 to 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were all 0 ppm.

Respirable Particulates (PM2_j)

Respirable particulate concentrations* indoors ranged between 21p.g/m3 to 38 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 33 pg/m^. This average concentration was below the USEPA recommended concentration for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration ranged from 21 to 30 pg/m3 with an average of 25 pg/m^.

CITY_21MC100_002891074

NYC-WTC_000396263

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000396263Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →