NYC 9/11 Public Portal Document
ATC Environmental, Inc.
104 East 25th Street
New York, New York 10010
NYC School Construction Authority Approved N.Y. State ELAP #10879
30-30 Thomson Avenue ACCREDITED NVLAP Lab Code # 1187
Long Island City, NY 11101 Report Date: 09/17/01
ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM)
With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS)
Method; AHERA Final Rule, EPA Federal Register (40 CFR. Part 763), Vol. 52, No. 210, October 30, 1987
Sample Identification Analysis Parameters
Proj ect/Site: World jrrade Centerj J2Y^^NY TEM Sample No.; 5515 - 59050
Personal Monitoring
Date Received: 09/r7/01 Grid Openings Analyzed; 10
Project- Sample No.z^O^l Average Grid Opening: 106.00 um
Air Volume; 480 liters Total Area Analyzed: 0.1124 mm2
Filter Type: MCE 25 mm diam., Pore Size: 0.45 um Analytical Sensitivity :X:9 s/mni2
Effective Area: 385 mm2 0.0071 s/cc
FIBROUS PARTICULATES ANALYZED
Number Observed CONCENTRATION
Total
Single Matrix Total. Struct. Filter Air
Fibers Bundles Clusters Struct. Struct >=5um Struct/rnm2 Struct/cc nam/m3
Chrysotile Asbestos 3 4 1 3 11 3 97.9 0.0785 2590
Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0
Ambiguous 0 0 0 0 0 0 0.0 0.0000 0
Total asbestos (includes ambiguous structures) 11 3 97.9 0.0785 2590
Non-Asbestos 0 0 0 0 D 0 0.0 0.0000 N/A
No Identification 0 0 . 0 0 0 0 0.0 0.0000 N/A
Totals (All Structures) 11 3 97.9 0.0785 N/A
The estimated uncertainty of this analysis is 1 standard deviation.
Non-asbestos fiber i.d. (EDS/SAED) : None detected
Amphibole Asbestos Type: None detected
The Analysis was carried out in accordance with the approved TEM method.
This laboratory is in compliance with the quality specified for the method.
Analyzed by: Report Reviewed by:
Marek Peysakhov Michael A. Gorycki, Ph.D.
Director of Electron Microscopy
CITY_21MC100_003265524