NYC 9/11 Public Portal Document

I. Introduction/Summary

Glomar Corp., Asbestos Testing and Consulting, was contracted by Newmark & Company, Real Estate, Inc., Mr. Bob Riggs, to perform Transmission Electron Microscopy (TEM) Air Quality Testing on various floors of the buildings at 40 Worth Street and 71 Thomas Street, New York, NY.

Testing was performed to determine the levels of asbestos fibers that may be present in the buildings. TEM sampling and test analysis was performed to insure that asbestos fibers, if present, would be detected.

In addition to the TEM Sampling and Testing, the temperature and relative humidity of area being tested was recorded.

Testing took place on January 28, 2002.

Glomar Corp. Technician, Mr. Sean Murray, was the on-site Air Monitoring Technician.

All air samples were collected by Glomar Corp and analyzed by Scientific Labs, New York, NY, a New York State approved Environmental Testing Laboratory. All samples were analyzed utilizing Transmission Electron Microscopy (TEM).

ALL SAMPLES TESTED "NSD" ( NO ASBESTOS STRUCTURES DETECTED).

II. Air Monitoring Criteria, Methods and Analysis

Air monitoring complied with Part 56 of Title 12 Sub-Part 56-17, Air Sampling Monitoring and Analysis of the Official Compilation of Codes, Rules and Regulations of the State of New York, Sub­ Part 56-17. Air Sampling Monitoring and Tknalysis requirements establishes schedules and methods that were followed by Glomar personnel. Tinalysis of Air Monitoring samples shall use (at a minimum) Phase Contrast Microscopy (PCM) or Transmission Electron Microscopy (TEM) using standards administered by the National Institute for Occupational Safety & Health (NIOSH) Method 7400 (PCM) and Method 7402 (TEM). Also followed is the New York State Department of Health Environmental Laboratory Approval Program (ELAP,) Item's 236-273. PCM analysis gives an index of Airborne fibers in the work place and TEM analysis gives an index of Asbestos Airborne Fibers in the work place.

See Appendix A for Air Sample Locations and Analysis

See Appendix B for Tested Areas Ten^rature & Relative Humidity Readings.

NYC-WTC_000322012

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000322012Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →