NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 1 page

Stuyvesant HS reoccupancy sampling summary, Sept 2002

Machine-extracted title · confidence 53%

Lead wipe sampling summary and ventilation unit testing results at Stuyvesant High School.

NYC-WTC_000321567
Page image
Scanned page image, NYC-WTC_000321567
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Date: September 4, 2002

To: Mr. Kelly McKinney, PE Associate Commissioner, Environmental Health NYC Department of Health and Mental Hygiene 125 Worth Street, Room 616, CN-32 New York, NY 10013

From: George Taylor

Subject: Summary of reoccupancy sampling and results performed at Stuyvesant HS, Chambers Street, New York, NY. (July 14 through August 31,2002)

1. Final Clearance Lead Wipe Sampling and Analysis. Analytical Method: EPA SW846-7420„— 9: 7 Clearance criteria, not to exceed:;^rug/^ e- 't 5

A. Unit Ventilators Number of unit ventilators tested: 262. Number of unit ventilators that exceeded clearance criteria and were re­ cleaned and re-sampled: 20. Number of unit ventilators that exceeded clearance criteria following re­ cleaning and re-sampling: 0.

B. Functional Spaces (Classrooms and corridors, offices, storage rooms, etc.) Number of functional spaces tested: 466. Number of functional spaces that exceeded clearance criteria and were re­ cleaned and re-sampled: 10. Number of functional spaces that exceeded clearance criteria following re­ cleaning and re-sampling: 0.

2. Final Clearance Air-Monitoring and Analysis. (Asbestos and Lead) Airborne Asbestos Analytical Method: TEM (AHERA Protocol). Clearance criteria: not to exceed 70 as/mm^.

A. Number of TEM Air-Samples Collected; 155.

B. Number of TEM Air-Samples that exceeded re-occupancy criteria: 0.

Airborne Lead Analytical Method: NIOSH 7082. Clearance criteria: not to exceed 1.5 ug/m’ or the method detection limit (NAAQS).

C. Number of airborne lead samples collected: 103.

D. Number of airborne lead samples collected that exceeded NAAQS : 6. Two locations, library and 10‘" floor corridor.

E. Number of airborne lead samples collected that exceeded NAAQS following re-cleaning and re-sampling: 0

CITY_21MC100_003051499

NYC-WTC_000321567

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000321567Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000434820

Summary of lead wipe sampling and re-occupancy results at Stuyvesant High School (July–Aug 2002).

Similar indexed content

Compare copies and versions →