To: Teachers, Students and Staff of Stuyvesant H.S ASSOCIATES INC.

From; Michael Parpounas, Vice President - ATC

CO: Bernard Orlan, Director E.H.S. - BOE

Date: 10/12/01 Re: Monitoring at Stuyvesant High School

Page 4 of 5

INDOOR AIR QUALITY

ATC commenced the lAQ assessment at Stuyvesant H.S. on October 9, 2001.

Temperature-. As of October 12, 2001, the indoor dry bulb temperature measurements ranged from 67.4 °F to 80.3 °F. Most of the measurements were within the range of 69 to 76 °F (at 50% relative humidity) recommended by ASHRAE Standard 55-1992 during heating season (wintertime conditions). The outdoor temperature range was 57 °F to 71.4 °F.

Relative Humidity: As of October 12,2001, the indoor relative humidity ranged from 28.2% to 61.9%. Most of the indoor measurements were within ASHRAE’s recommended range of 30 to 60% for occupant comfort. The outdoor relative humidity range was 26.8% to 59.9%.

Carbon Dioxide Concentration: As of October 12,2001, the indoor CO2 concentrations ranged from 404 ppm to 2025 ppm. The outdoor (background) CO2 concentration range was .. 338 ppm to 395 ppm. Therefore, the acceptable level of CO2 at this location was 1038 ppm to 1 1095 ppm (background level + 700 ppm). Levels measured above each day's acceptable level were in fully occupied classrooms. Levels above the recommended maximum do not indicate a health risk. CO2 measurements are used as an indicator of available outdoor air. Therefore, due to the restricted intake of outdoor air, elevated CO2 levels are to be expected. The primary source of CO- indoors is occupant respiration.

Carbon Monoxide Concentration: As of October 12, 2001, the indoor CO concentrations ranged from 0 ppm to 5 ppm*. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm to 2 ppm.

Respirable Particulates: As of October 12,2001, the indoors respirable particulate concentrations ranged between 10 pg/m^ and 55 pg/m®*. All but one of these concentrations were below the NPAAQS/ASHRAE guideline of 50 pg/m^ (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter) except one concentration of 55 pg/m^ collected in Room # 351 on October 10, 2001. The outdoor respirable particulate concentrations range was 16 pg/m^ and 42 pg/m^

TVOC Concentration: As of October 12, 2001, indoor TVOC concentrations were 0.0 ppm for all readings. These concentrations were below the AIHA guideline of 1 ppm for non-industrial buildings. The outdoor TVOC concentration was also 0.0 ppm.

* The 5ppm of CO and 55 pg/m^ of respirable particulate levels were the result of a classroom experiment in Room 351 (Plastics and Wood Technologies) in which material was being burned at the time of the testing.

CITY_21MC100_003036290

NYC-WTC_000321457

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000321457Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000256164

Indoor air quality measurements conducted at Stuyvesant High School.

Similar indexed content

NYC-WTC_000256013

ATC memo accompanying IAQ report for Stuyvesant High School, February 12, 2002.

Similar indexed content

Compare copies and versions →