Ambient air testing, high school lead and dust

Machine-extracted title · confidence 37%

Ambient air testing and settled dust/bulk sampling for asbestos at a high school facility.

NYC-WTC_000320841–000320847
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

HIGH SCHOOL FOR LEADERSHIP & PUBLIC SERVICE TEM AMBIENT AIR TESTING SETTLED DUST BULK WATER SAMPLING (Structure/mm^) SAMPLING FOR ASBESTOS Date # of Sample Results of TEM #of Results of Settled Dust #of Results Collected Asbestos Sample Bulk Sample for Samples Analysis Asbestos (structure/mm^)

12/29/01 9 Two structures (44.48 S/mm^) were detected inside the library on the 1 S'" floor. 01/10/02 21 No evidence of total coliform bacteria in the drinking water supply. 21 Potable water sampling. All samples contain elevated color level (over 15 color) and free residual chlorine are below the range established by the NYCDEP._____________ 42 Analysis for metals. Lead. copper, and iron (first draw) were above the NYSDOH MCL. All samples taken after the 30- second flush were below the 30-minute threshold. 01/23/02 21 Potable water sampling for color. Levels of color in water in all water outlets were below the NYSDOH MCL. 01/27/02 14 No structures detected 02/04/02 18 No structures detected 02/05/02 18 No structures detected 02/06/02 18 No structures detected 02/07/02 18 No structures detected 02/08/02 18 No structures detected 02/09/02 18 No structures detected 02/10/02 18 No structures delected 02/11/02 18 One stracture was detected (<22.34 S/mm^) in the basement adjacent to exit tfom gym. 02/12/02 18 No structures detected 02/13/02 18 No structures detected 02/14/02 18 No structures detected 02/15/02 18 No structures detected 02/16/02 18 No structures detected 02/17/02 18 No structures detected 02/18/02 18 No structures detected 02/19/02 18 No structures detected 02/20/02 18 2 structures (44.48 s/mm^) were detected in one sample which was collected along the west side of the student cafet. On the 14“' floor. 02/21/02 18 No structures detected 02/22/02 18 No structures detected 02/23/02 18 Elevated level of asbestos fibers (956.41 s/mm^ was found on the 2““ floor auditorium. - south side. 02/24/02 18 Elevated level of

CITY_21MC100_003051102

NYC-WTC_000320841

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000320841Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000320880

Ambient TEM and bulk asbestos results, with settled dust findings at PS150M.

Similar indexed content

NYC-WTC_000320873

Ambient TEM results and bulk sampling for asbestos across multiple dates at PS150M.

Similar indexed content

NYC-WTC_000320852

Asbestos TEM and bulk sampling results for a NYC public school, with debris and roof sampling.

Similar indexed content

Compare copies and versions →