Mr. Bernard P. Orlan June 4, 2002
Indoor Air Quality Assessment Page 3
P. S. 234M ATCPrpiectNpa5-1912fr:0279
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one
(51) from inside the school building and nine (9) outdoors. All three floors of the school were
surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 7:00 AM and concluded after
12:36 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 72.3 °F to 76.3 °F. Fifteen (15) of the
indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative
humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The
outdoor temperature measurements ranged from 68.2 °F to 68.4 °F.
Relative Humidity
The relative humidity indoors ranged from 24.1 percent to 36.3 percent. Thirty (30) of the
indoor measurements for relative humidity were below the ASHRAE-recommended range of 30
to 60 percent for occupant comfort. The outdoor relative humidity ranged from 33.6 percent to
33.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 546 ppm to 1361 ppm. One (1) of the indoor
measurements was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 610 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1310 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 1 ppm for all readings. These concentrations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was also 1
ppm for all readings.
Respirable Particulates (PM2 5)
Respirable particulate concentrations* indoors ranged between 5 pg/m^ to 12 pg/m^ with an
average approximately 9 pg/m^- None of the measurements collected indoors for respirable
particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor
respirable particulate concentration ranged from 14 pg/m^ to 16 pg/m^ with an average of
approximately 16 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.