NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan June 4, 2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Project No. 15-19125-0279
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO2, CO, and TVOCs were below applicable standards and guidelines.
2. Fifteen (15) of the indoor measurements for temperature were below the range of 73 to 79°F
(at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the
summer season.
3. Thirty (30) of the indoor measurements for relative humidity were below the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. None of the measurements collected indoors for respirable particulate concentrations were
above the NPAAQS 65 ug/m^ 24-hour average concentration of particulate matter 2.5
micrometers or less in aerodynamic diameter and the USEPA recommended concentration of
40 pg/m3 for sensitive individuals and children.
5. One (1) CO2 measurement was above the range recommended by ASHRAE 62-1999.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or212.
Sincerely,
A TC ASSOCIA TES INC.
/ Yiannis Eistathi
Senior Project Manager
Attachment
CITY_21MC100_0 03032620
NYC-WTC_000315313