Mr. Bernard P. Orlan March 13, 2002
Indoor Air Quality Assessment Page 4
P. S.234M ATC Project No. 15-19125-0279
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO ,CO2and TVOCs were below applicable standards and guidelines.
2. All of the indoor PM2.5 measurements were below the NPAAQS of 65 pg/m^ or the USEPA
recommended PM2.5 concentration of 40 pg/m^ for sensitive individuals and children.
3. Forty-six (46) indoor measurements for relative humidity were below and five (5) were
within the ASHRAE recommended range of 30 to 60 percent for occupant comfort.
4. Eight (8) of the temperature measurements were above and forty-three (43) were within the
range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard
55-1992,during the heating season (wintertime conditions).
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
336 or 212.
Sincerely,
A TC ASSOCIA TES INC.
Reviewed by:
Amel Javi James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division