Mr. Bernard P. Orlan March 13, 2002
Indoor Air Quality Assessment Page 3
P. S. 234M______________________________ ATC Project No. 15-19125-0279
Real-Time environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one
(51) from inside the school building and nine (9) outdoors. All three floors of the school were
surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after
4:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.4 °F to 78.4 °F. Eight (8) indoor
measurements for temperature were above and forty-three (43) measurements were within the
range of 68 to 75 °F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-
1992 during the heating season (wintertime conditions). The outdoor temperature measurements
ranged from 38.4 to 51.8 °F.
Relative Humidity
The relative humidity indoors ranged from 23.1 percent to 37.6 percent. Forty-six (46) indoor
measurements for relative humidity were below and five (5) measurements were within the
ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative
humidity ranged from 32 to 36.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 407 ppm to 854 ppm. All of the
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 463 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1163 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors are 0 ppm for all readings. These concentrations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from
0-2 ppm.
Respirable Particulates CPM2j)
Respirable particulate concentrations* indoors ranged between 17 pg/m^ to 36 pg/m^. All
measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5
concentration for the entire school building was approximately 24 pg/m^. This average
concentration was below the USEPA recommended concentration for sensitive individuals such
as asthmatic people and children. The outdoor respirable particulate concentration ranged from
49 to 54 pg/m3 with an average of 52 pg/m^.