Mr. Bernard P. Orlan February 26, 2002
Indoor Air Quality Assessment Page 3
P. S. 234M________ ATC Project No. 15-19125-0279
real-time environmental measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one
(51) from inside the school building and nine (9) outdoors. All three floors of the school were
surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after
3:55 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 62.9 °F to 80.8 °F. Twenty-three (23)
measurements were above and nine (9) were below the range of 68 to 75°F (at 50 percent
relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season
(wintertime conditions). The outdoor temperature measurements ranged from 51.9 to 53.2 °F.
Relative Humidity
The relative humidity indoors ranged from 21.0 percent to 31.9 percent. Forty-two (42)
of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity ranged from 23.5 to 26.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 505 ppm to 957 ppm. All of the
measurements were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 475 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1175 ppm (background level + 700 ppm). The highest measurement was recorded
in room 222. Levels above the recommended maximum do not indicate a health risk. Carbon
dioxide measurements are used as an indicator of available outdoor air. The primary source of
CO2 indoors is occupant respiration. ■
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1
ppm.
Respirable Particulates (PM2 5) ,
Respirable particulate concentrations* indoors ranged between 9 pg/m^ to 30 pg/m^. All
measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5
concentration for the entire school building was approximately 18 pg/m^. This average
concentration was below the USEPA recommended concentration for sensitive individuals such
as asthmatic people and children. The outdoor respirable particulate concentration ranged from
24 to 49 pg/m^ with an average of 31 pg/m^.