Mr. Bernard P. Orlan February 26, 2002
Indoor Air Quality Assessment Page 4
P. S.234M ATC Project No. 15-19125-0279
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOCConcenU^atim
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO, CO2 and TVOCs were within applicable standards and guidelines.
2. None of the PM2.5 measurements were above Ihe NPAAQS of 65 pg/m^. Only one (1)
outdoor measurement was above the USEPA recommended PM2.5 concentration of 40
pg/m- for sensitive individuals and children.
3. Forty-two (42) of the indoor measurements of relative humidity were below the ASHRAE
recommended range of 30 to 60 percent for occupant comfort.
4. Twenty-three (23) of the temperature measurements were above and nine (9) were below the
range of'68 to 75°F (at 50 percent relative hiunidity) as recommended by ASHRAE Standard
55-1992 during the heating season (wintertime conditions).
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.
Sincerely,
ATC ASSOCIATES INC.
Reviewed by:
r
Yiannis Efstathiou James R. Cohn, CEH, CSP
Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_003031828