NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, PS 89M, Apr 23, 2002

Machine-extracted title · confidence 42%

Indoor air quality measurements collected for evaluation at PS 89M.

NYC-WTC_000313524–000313527
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Ek'inard P. Orlan April 24, 2002 Indoor .Air Quality Assessment Page 3 __________________________________ __ AApieeiNm !5-19125-029" It f. A L-T I .A IE F. N VIR () y M E IA I. MEA S 1 R E A1V. A 1 .S

ATC collected eighty (SO) sets of real-time environmental measurements consisting of seventy (7i)) from inside the .‘chool building and ten (10) from outdoors. .All five doors of the school building w ere surveyed. 1 hese results are described below.

Field data sheets are found in Altachment 1. Readings began at 8:00 .A.M. and concluded at approximately 11:30 A.M.

Tefiiperaiiire

Indoor dry bulb temperature measurements ranged from 64 1' to 70.S °F. Ail of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASFIRAE Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 46.8 °F to 48.1 °F.

Rekilive Humidi/y

The relative humidity indoors ranged from 24.6 to 36.5 percent. Sixty (60) of the indoor measurements for relative humidity were below and ten (10) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 31.8 to 34.3 percent.

Carbon Dioxide Coriceiifralioii

Carbon dioxide concentrations indoors ranged from 472 ppm to 1050 ppm. All of the indoor measurements for CO2 were below above the ASFIRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 455 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1155 ppm (background level + 700 ppm), keveks above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO? indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Coiiccnlraiion

Carbon monoxide concentrations indoors was 0 ppm for all readings. These concentrations were below the NPAAQS/ASFIRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm for all collected readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 5 pg/m^ to 17 ug/nP. The a verage PM2 5 concentration for the entire school building was approximately 9 g/m^. All of the indoor and outdoor measurements were below the NPAAQS of 6.5 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the IJSEP.A recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 16 to 20 pg/m^ with an average of 18 pg/m^.

CITY_21MC100_003047607

NYC-WTC_000313526

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000313526Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →