NYC-WTC_000394514
IAQ measurements collected April 30, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗IAQ measurements collected April 25, 2002 at the referenced school.
NYC-WTC_000394477–000394480OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 26, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M________________________________ ATCProiectNoJ5J^125-0297 Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 64.3 °F to 76.1 °F. Sixty-nine (69) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 53.1°F to 53.5°F.
Relative Humidity
The relative humidity indoors ranged from 34.1 to 38.7 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 33.6 to 33.9 percent.
Carbon Dioxide Conceniraiion
Carbon dioxide concentrations indoors ranged from 510 ppm to 1112 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 461 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1161 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 1 ppm for all collected readings.
Respirable Particulates (PM2^5)
Respirable particulate concentrations* indoors ranged between 13 pg/m^ to 21 ug/m^. The average PM2.5 concentration for the entire school building was approximately 17 g/m^. All of the indoor and outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 21 to 23 pg/m^ with an average of 22 pg/m^.
CITY_2IMCl0 0_0 00490162 NYC-WTC_000394479
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000394514
IAQ measurements collected April 30, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394489
Indoor air quality report for PS 89M with April 26, 2002 measurements.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199027
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313589
Indoor air quality measurements collected at PS 89M for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313568
Indoor air quality measurements collected at PS 89M for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369857
Indoor air quality report for PS/89M school, measurements collected May 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313667
ATC measurements for PS 89M on May 15, 2002, temperature and humidity.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369254
IAQ parameters with temperature, humidity, and gas readings.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394465
April 2002 IAQ report for P.S. 89M, with BOE-referenced measurements.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369833
ATC report of IAQ measurements at P.S. 89M requested by BOE, dated May 21, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392864
ATC report of IAQ measurements at PS 89M requested by BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369801
ATC IAQ measurements at PS 89M for BOE; May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000178791
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on June 18, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328397
ATC IAQ measurements collected May 29, 2002 at PS 89M, BOE requested.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313873
ATC indoor air quality measurements conducted June 13, 2002 for NYC BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392743
ATC IAQ measurements conducted at P.S. 89M for NYC BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313568
Indoor air quality measurements collected at PS 89M for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394514
IAQ measurements collected April 30, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000394514
IAQ measurements collected April 30, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000394489
Indoor air quality report for PS 89M with April 26, 2002 measurements.
Similar indexed content
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 22, 2002.
Similar indexed content
NYC-WTC_000313589
Indoor air quality measurements collected at PS 89M for BOE.
Similar indexed content
NYC-WTC_000313568
Indoor air quality measurements collected at PS 89M for BOE.
Similar indexed content