NYC 9/11 Public Portal Document
104 East 25th Street 10th FL
(SRK
New York, New York 10010
www.atc-enviro.oom
212.353.8280
Fax 212.353.g306
ASSOCIATES INC.
November 19, 2001
Mr. Bernard P. Orlan
Director, Environmental Health & Safety
New York City Board of Education
28-11 Queens Plaza North
Long Island City, NY 11101-4008
Re: Indoor Air Quality Assessment
Stuyvesant High School (M477)
345 Chambers Street
New York, New York 10007
ATC Project No. 15-19125-0246
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of an indoor air quality (lAQ)
assessment conducted on November 16, 2001, at the referenced school. The New York City
Board of Education (BOE) requested this assessment to determine if acceptable indoor air
quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity,
carbon dioxide (CO,) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates were also measured.
Tenzin Namgyal and Wagdi Abdelshahid, Industrial Hygienists, of ATC’s New York City office,
conducted the assessment. ATC’s findings and conclusions are based on a visual inspection,
real-time environmental measurements and conditions present in the school at the time of the
assessment.
ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551,
manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates with a Dust-Trak® Aerosol Monitor
Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a R.AE Systems. Inc. MiniRAE® photoionization
detector (PID).
CITY_21MC100_003045968
NYC-WTC_000312094
OCR can misread numbers and units. Confirm readings against the page image before using them.