Mr. Bernard P. Orlan October 10, 2001 Indoor Air Quality Assessment Page 3 StuvA^esantH.S. ('Mamanan) ATC Project No. 15-19125-0246
SAMPLING RESL L I S
Real-Time Environmental Measurements
ATC collected one hundred-four (104) sets of real-time environmental measurements consisting of one hundred-two (102) in the school building and two (2) outdoors. These results are described below. Field data sheets are found in Attachment 1.
Temperature
Indoor dry bulb temperature measurements ranged from 67.4 °F to 78.1 °F. Measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). A few rooms on the 3’’^ and 5th floors were slightly below the recommended range. The outdoor temperature range was 57 to 64.7°F.
Relative Humidity
The relative humidity indoors ranged from 28.2 percent to 46.8 percent. Most of the indoor measurements were within ASHRAE’s recommended range of 30 to 60 percent for occupant comfort. A few rooms on the 3’’*^ and fib floors were slightly below the recommended range. The outdoor relative humidity range was 26.8 to33.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 446 ppm to 2025 ppm. Three COn measurements were at or above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration range was 373 to 395 ppm. Therefore, the acceptable level of CO2 at this location was 1095 ppm (background level 700 ppm). Eight measurements were within 10% of the 1095 ppm level and twenty-three (23) exceeded 900 ppm. The highest level measured (2025 ppm) was in a fully occupied classroom (Room 429). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 - Ippm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 - 1 ppm.
Respirable Particulates
Respirable particulate concentrations indoors ranged between 10 gg/m^ and 39 pg/'m^ . The concentrations of all samples were below the NPAAQS/ASHRAE guideline of 50 pg/m^ (annual average concentration of particulate matter 10 micrometers or less in aerodjmamic diameter). The outdoor respirable particulate concentration range was 20 to 30 ug/m<
CITY_21MC100_003045487
NYC-WTC_000311689
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000271057
Letter discussing Stuyvesant High School project and related communications.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311748
IAQ assessment report for Stuyvesant High School dated October 15, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292885
IAQ field report for Stuyvesant High School dated Oct 16, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292880
Cover letter presenting IAQ field report for Stuyvesant HS.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197534
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311732
Indoor air quality assessment conducted October 12, 2001 at Stuyvesant High School.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271099
Indoor air quality assessment results for Stuyvesant HS dated Oct 12, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271114
Indoor air quality assessment conducted at Stuyvesant High School.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188511
Letter from ATC Associates providing an indoor air quality assessment report for Stuyvesant High School dated October 12, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292854
IAQ assessment report for Stuyvesant High School, dated Oct 11, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000329843
IAQ assessment report for PS 130M school building.
10 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311765
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
11 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000311748
IAQ assessment report for Stuyvesant High School dated October 15, 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188511
Letter from ATC Associates providing an indoor air quality assessment report for Stuyvesant High School dated October 12, 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292885
IAQ field report for Stuyvesant High School dated Oct 16, 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370389
ATC Associates report of IAQ measurements at High School for Leadership & STEAM, 90 Trinity Place, Mar 1, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199187
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 234M on April 11, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000217725
ATC Associates letter reporting indoor air quality measurements collected at P.S. 234M on March 1, 2002, as requested by the NYC Board of Education.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000271057
Letter discussing Stuyvesant High School project and related communications.
Similar indexed content
NYC-WTC_000311748
IAQ assessment report for Stuyvesant High School dated October 15, 2001.
Similar indexed content
IAQ field report for Stuyvesant High School dated Oct 16, 2001.
Similar indexed content
NYC-WTC_000292880
Cover letter presenting IAQ field report for Stuyvesant HS.
Similar indexed content
NYC-WTC_000197534
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.
Similar indexed content