NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan February 12, 2002
Indoor Air Quality Measurements Page 4
Stuyvesant High School (M477)________________________ ATCProiectNoM5H9125^^
concentration range for these rooms was 14-17 pg/m^ with an average of approximately 16
pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Measurements of temperature and concentrations of respirable particulates, CO2, CO and
TVOCs, were within applicable standards and guidelines.
2. One hundred and three (103) measurements of relative humidity were below the ASHRAE
recommended range of 30 to 60 percent for occupant comfort.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.
Sincerely, Reviewed by:
A TC ASSOCIA TES INC.
■
Yiannis Efstathiou James R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CITY_21MC100_003045338
NYC-WTC_000311558