NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan February 12, 2002
Indoor Air Quality Measurements Page 3
Stuwesant High School (’M477) ATC Project No. 15-19125-0246
Real-Time E^\IRO^MEMAL Mea^rements
ATC collected one hundred and twenty-one (121) sets of real-time environmental measurements
consisting of one hundred and nineteen (119) in the school building and two (2) outdoors. All
ten floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after
1:50 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.7°F to 73.9°F. All of the
measurements were within the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
The outdoor temperature range was 40.8 to 43.9 °F.
Relative Humidity
The relative humidity indoors ranged from 25.4 percent to 30.9 percent. One hundred and three
(103) of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity levels were 53.4 and 55.7 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 519 ppm to 1126 ppm. All of the CO2
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 544 and 531 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1244 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0
to 1 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 21 pg/m^ with an
average of approximately 16 pg/m^. None of the measurements were above the NPAAQS of 65
pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter or the USEPA recommendation of 40 pg/m^ for sensitive individuals and
children. The outdoor respirable particulate concentrations were 36 and 38 pg/m^.
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency
Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5
CITY_21MC100_003045337
NYC-WTC_000311557
OCR can misread numbers and units. Confirm readings against the page image before using them.