NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, Stuyvesant HS, Feb 2002

Machine-extracted title · confidence 52%

ATC indoor air quality measurements report for Stuyvesant High School dated Feb 14, 2002.

NYC-WTC_000402004–000402007
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

104 East 25th St New York, New York 10010 www.atc-enviro.com 212.353.8280 Fax 212.353.8306 ASSOCIATES INC.

February 15, 2002

Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education .28-11 Queens Plaza North Long Island City, NY 11101-4008

Re: Indoor Air Qualify Assessment Stuyvesant BUgh School (M477) 345 Chambers Street New York, New York 10007 ATC Project No. 15-19125-0246

Dear Mr. Orlan;

ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on February 14, 2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.

SCOPE OF WORK

ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (COj) and carbon monoxide (CO).

Total volatile organic compounds (TVOCs) and respirable particulates were also measured.

Herant Antonyan, Industrial Hygienist, of ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.

ATC measured temperature, relative humidity, COj and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.

ATC measured concentrations of respirable particulates (PM2,5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.

ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).

The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of

CITY_21MC100_002923367

NYC-WTC_000402004

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000402004Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000311555

ATC IAQ measurements report for Stuyvesant High School, Feb 2002.

Similar indexed content

Indoor air quality report, February 2002

NYC-WTC_000197500

Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in February 2002.

Similar indexed content

NYC-WTC_000336438

Indoor air quality measurements documented for Stuyvesant HS.

Similar indexed content

NYC-WTC_000311536

ATC IAQ measurements report for Stuyvesant High School, Feb 2002.

Similar indexed content

Compare copies and versions →