Mr. Bernard P. Orlan February 4. 2002 Air Sampling for Dioxins Page 2 H. S. of Economics & Finance (833M1 ATC Project No. 15-19125-0291

Combustion of PCB-containing oils, such as during an electrical transfonner fire, is knowm to produce dioxins. Burning of some plastics may also produce dioxins. Dioxins are toxic and are considered to be carcinogenic.

The Environmental Protection Agency (EPA) has a screening level for dioxins in air of 0.16 nanograms per cubic meter (0.16 ng/m^). A nanogram is a thousandth of a microgram (1 X IO'*' gram). The EPA screening level is based on continuous exposure for one year. The Occupational Safety and Health Administration (OSHA) ha.s not established a Pemiissible Exposure Limit (PEL) for dioxins in air.

RESULTS

Each sample was analyzed for seventeen (17) PCDD/PCDF isomers. The results for each isomer were then converted to 2, 3, 7, 8 -tetrachloro-dibenzo-p-dioxin (2, 3, 7, 8-TCDD) equivalents by multiplying-by an established equivalency factor. This provides a single value for the analytical results for each sample.

The results are summarized in the table. A picogram is one one-thousandth of a nanogram (10’’’ gram).

AIRBORNE DIOXIN LEVELS (2,3, 7, 8 TCDD EQUIVALENTS)

Outdoors by Main Entrance 0.027 Pl Main Lobby 0.015 ________ P2___________ 3f‘* Floor Hallway by Stair B 0.00097 P3 5“ Floor Stair A 0.0016 P4__________ 7^'’ Floor Hallway by Bridge 0.0014 P5 S"’ Floor Kitchen 0.019 P6 9‘‘' Floor Room 906 0.016 P7 10*^ Floor Room 1006 0.022 P8 Roof 0.0013 P9 Field Blank 0.00 PIO

CITY_21MC100_003029015

NYC-WTC_000310758

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000310758Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →