Mr. Bernard P. Orlan March 1,2002
Air Sampling for Metals Page 2
P.S. 234 ('Manhattan ) ATC Project No. 15-19125-0279
Results
Chromium (Cr) was the only metal detected in all four samples and in the blank. Aluminum (Al)
was detected in one sample and and iron (Fe) was detected in two samples. Blank-correcting the
Cr levels substantially reduces the airborne concentrations
The results are shown in the following table:
METALS IN AIR CONCENTRATIONS
FEBRUARY 19, 2002
■I CHRO r
(«g/ IRON
(ugW) Blank-c( ___ IB
Main Lobby / Ml 0.477 0.019 *BDL 2.10
E'floor Hallway/
M2 0.599 0.142 BDL BDL
West Playground/
M3 0.533 0.076 2.70 3.05
Roof/M4 0.477 0.019 BDL BDL
Field Blank/M5
ug/sample 0.549 BDL BDL
* Below Detection Limit
All of the blank-corrected Cr concentrations are below the EPA screening level of 0.6 ug/m^. The
EPA has no screening levels or guidelines for Al or Fe in ambient air.
ATC appreciates the opportunity to provide this indoor air quality service to the BOE. Please call
me at (212) 353-8280 extension 212 if you have any questions.